When the PLC determines that it has a valid connection to the ConveyLinx-ECO in question and is ready for it to respond to output data being written by the PLC:

  • Your PLC program needs to move the value in the Current Module Reset Counter register into the Set Module Reset Counter register

  • When the ConveyLinx-ECO detects that the value in Set Module Reset Counter register is equal to the value in the Current Module Reset Counter register; the module will respond to data being written by the PLC to the remaining output assembly registers.