This chart shows the assembled registers for the data coming from the ConveyLinx Module in PLC I/O Mode and provided as input to the PLC:

Register Name / Module Address Assembled Address for PLC Links
ConveyStop Status Word
4:0019
M: 4:1700
E: I.Data[0]
P: Byte 0 (Hi)
   Byte 1 (Lo)
ConveyStop Status
Sensor & Control Port Inputs
4:0035
M: 4:1701
E: I.Data[1]
P: Byte 2 (Hi)
   Byte 3 (Lo)
Sensor & Control Ports
Sensor Detect
4:0036
M: 4:1702
E: I.Data[2]
P: Byte 4 (Hi)
   Byte 5 (Lo)
Sensor & Control Ports
Module Voltage
4:0024
M: 4:1703
E: I.Data[3]
P: Byte 6 (Hi)
   Byte 7 (Lo)
Sensor & Control Ports
Left Motor Current
4:0055
M: 4:1704
E: I.Data[4]
P: Byte 8 (Hi)
   Byte 9 (Lo)
Left Motor Status
Left Motor Frequency
4:0056
M: 4:1705
E: I.Data[5]
P: Byte 10 (Hi)
   Byte 11 (Lo)
Left Motor Status
Left Motor Temperature
4:0057
M: 4:1706
E: I.Data[6]
P: Byte 12 (Hi)
   Byte 13 (Lo)
Left Motor Status
Left Motor Status
4:0058
M: 4:1707
E: I.Data[7]
P: Byte 14 (Hi)
   Byte 15 (Lo)
Left Motor Status
Right Motor Current
4:0079
M: 4:1708
E: I.Data[8]
P: Byte 16 (Hi)
   Byte 17 (Lo)
Right Motor Status
Right Motor Frequency
4:0080
M: 4:1709
E: I.Data[9]
P: Byte 18 (Hi)
   Byte 19 (Lo)
Right Motor Status
Right Motor Temperature
4:0081
M: 4:1710
E: I.Data[10]
P: Byte 20 (Hi)
   Byte 21 (Lo)
Right Motor Status
Right Motor Status
4:0082
M: 4:1711
E: I.Data[11]
P: Byte 22 (Hi)
   Byte 23 (Lo)
Right Motor Status
Left Motor Port Digital I/O Status
4:0060
M: 4:1712
E: I.Data[12]
P: Byte 24 (Hi)
   Byte 25 (Lo)
Motor Ports Digital Status
Right Motor Port Digital I/O Status
4:0084
M: 4:1713
E: I.Data[13]
P: Byte 26 (Hi)
   Byte 27 (Lo)
Motor Ports Digital Status
Upstream Module Status
4:0134
M: 4:1714
E: I.Data[14]
P: Byte 28 (Hi)
   Byte 29 (Lo)
Upstream / Downstream Status & Tracking
Downstream Module Status
4:0232
M: 4:1715
E: I.Data[15]
P: Byte 30 (Hi)
   Byte 31 (Lo)
Upstream / Downstream Status & Tracking
Current Tracking Word 1 for Adjacent Upstream Module
4:0139
M: 4:1716
E: I.Data[16]
P: Byte 32 (Hi)
   Byte 33 (Lo)
Upstream / Downstream Status & Tracking
Current Tracking Word 2 for Adjacent Upstream Module
4:0140
M: 4:1717
E: I.Data[17]
P: Byte 34 (Hi)
   Byte 35 (Lo)
Upstream / Downstream Status & Tracking
Current Module Reset Counter
N/A
M: 4:1718
E: I.Data[18]
P: Byte 36 (Hi)
   Byte 37 (Lo)
Upstream / Downstream Status & Tracking
Left Motor Servo Position
4:0062
M: 4:1719
E: I.Data[19]
P: Byte 38 (Hi)
   Byte 39 (Lo)
Servo Control Status
Right Motor Servo Position
4:0086
M: 4:1720
E: I.Data[20]
P: Byte 40 (Hi)
   Byte 41 (Lo)
Servo Control Status
Left Motor Servo Status
4:0011
M: 4:1721
E: I.Data[21]
P: Byte 42 (Hi)
   Byte 43 (Lo)
Servo Control Status
Right Motor Servo Status
4:0016
M: 4:1722
E: I.Data[22]
P: Byte 44 (Hi)
   Byte 45 (Lo)
Servo Control Status