In this example we have the Left Line configured as standard spur angle merge and the Merge Priority to be Center Line

The Merge Zone is the upstream zone of ConveyLinx-Ai Family Modules 192.168.25.28 and the Left Line’s most downstream node is 192.168.24.31 and we want this line to have the Merge Line Full function enabled. On the Left Line, we would like for the upstream zone of ConveyLinx-Ai Family Modules 192.168.24.25 to be the Merge Line Full function’s Monitor Zone. We would also like that once the Monitor Zone has been accumulated (or blocked) for 5 seconds, we want the Left Line to release for 5 seconds and then return the priority to the Center Line. Here is the ConveyMerge Configuration Screen with the values entered for this example: