Please Note – ConveyMerge works for ALL ConveyLinx Family Modules
Module | Firmware |
---|---|
ConveyLinx-ERSC | 4.25 and later |
ConveyLinx-HTF | 4.25 and later |
ConveyLinx-Ai2 | 4.20 and later |
ConveyLinx-Ai3-24-xx | 4.20 and later |
The following items are the prerequisites and constraints required to provide a fully functioning automatic conveyor merge:
- EasyRoll version 4.3 or greater
- Only (1) one Merge Zone is allowed for any given single module
- Merge Zone cannot have any Extension (slaved) zone
- Merge Zone must be in ZPA mode. Left Line discharge, Right Line discharge, and Center Line discharge can be in either ZPA mode or PLC I/O mode
- Left, Right, and Center Lines discharges cannot also be included in another instance of ConveyMerge