PLC Developers Guide / ZPA Mode Control / PLC Inputs for ZPA Mode
ConveyStop Status |
ConveyLinx ERSC ✅ | ConveyLinx-Ai 24V ✅ | ConveyLinx-Ai 48V ✅ |
ConveyLinx-ECO ✅ | ZPA Mode ✅ | PLC I/O Mode ❌ | |
Register Name | Internal Address | Assembled PLC Address | Description | ||
Reserved | M: 4:1519 E: I.Data [19] P: Byte 38 (Hi) P: Byte 39 (Lo) |
Used for Reset Protection connection See topic Assemblies with Reset Protection for details |
|||
ConveyStop Status | 4:0019 | M: 4:1520 E: I.Data [20] P: Byte 40 (Hi) P: Byte 41 (Lo) |
Bitwise Value | ||
bit 00 thru bit 04 – Reserved | |||||
bit 05 = | Stop active on another module in Stop Group | ||||
bit 06 = | Stop active due to lost communication connection | ||||
bit 07 = | Stop active due to lost PLC connection | ||||
bit 08 = | Reserved | ||||
bit 09 = | Reserved | ||||
bit 10 = | Stop active due to Stop Command from PLC | ||||
bit 00 thru bit 04 – Reserved |