PLC Developers Guide / ZPA Mode Control / PLC Inputs for ZPA Mode


ConveyStop Status

ConveyLinx ERSC ConveyLinx-Ai 24V ConveyLinx-Ai 48V
ConveyLinx-ECO ZPA Mode PLC I/O Mode


Register Name Internal Address Assembled PLC Address Description
Reserved N/A M: 4:1519
E: I.Data [19]
P: Byte 38 (Hi)
P: Byte 39 (Lo)
Integer Value
Used for Reset Protection connection
See topic Assemblies with Reset Protection for details
ConveyStop Status 4:0019 M: 4:1520
E: I.Data [20]
P: Byte 40 (Hi)
P: Byte 41 (Lo)
Bitwise Value
Bit 00 = Reserved
Bit 01 = Reserved
Bit 02 = Reserved
Bit 03 = Reserved
Bit 04 = Reserved
Bit 05 = Stop Active on another module in Stop Group
Bit 06 = Stop Active due to lost communication connection
Bit 07 = Stop Active due to lost PLC connection
Bit 08 = Stop active on Left Control Port
Bit 09 = Stop active on Right Control Port
Bit 10 = Stop Active due to lost PLC connection
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved