Register Name / Module Address | Assembled Address for PLC | Description |
---|---|---|
Set Status to Downstream Module 4:0196 |
M: 4:1817 E: O.Data [17] P: Byte 34 (Hi) Byte 35 (Lo) |
Used to write this module’s ZPA Status to its neighboring Downstream module: |
4 = Instruct Downstream module to “wake-up” and run its most upstream zone | ||
1 = Instructs Downstream module that carton has exited local zone and to accept any tracking data written in Set Discharge Tracking Word 1 / Word 2 registers when carton arrives | ||
Set Status to Upstream Module 4:0116 |
M: 4:1818 E: O.Data [18] P: Byte 36 (Hi) Byte 37 (Lo) |
Used to write this module’s ZPA Status to its neighboring Upstream module: |
5 = Instructs Upstream module’s discharge zone to accumulate and hold any carton that arrives at its discharge zone. | ||
1 = Instructs Upstream module’s discharge zone to release any carton that arrives at its discharge zone | ||
Set Discharge Tracking Word 1 4:0201 |
M: 4:1820 E: O.Data [20] P: Byte 40 (Hi) Byte 41 (Lo) |
Only used when local PLC I/O Mode module needs to pass tracking data to a downstream connected ConveyLinx-Ai Family Modules. Used in conjunction with Set Status to Downstream Module register |
Set Discharge Tracking Word 2 4:0202 |
M: 4:1821 E: O.Data [21] P: Byte 42 (Hi) Byte 43 (Lo) |
|
Reserved | M: 4:1822 E: O.Data [22] P: Byte 44 (Hi) Byte 45 (Lo) |