Once you have established that ATevo is undamaged, identify unit enclosure style using the table below. For enclosure specifications and dimension details, see Outline Drawing links – formatted like (JE5###-00) in the table.
| OUTPUT | 24 Vdc | 48 Vdc | 130 Vdc | 260 Vdc |
|---|---|---|---|---|
| 16 Adc | n/a | n/a | n/a | 5070 (JE5331-00) |
| 25 Adc | n/a | n/a | 5070 (JE5331-00) | 5070 (JE5331-00) |
| 30 Adc | n/a | n/a | 5070 (JE5331-00) | n/a |
| 40 Adc | n/a | n/a | 5070 (JE5331-00) | n/a |
| 50 Adc | 5070 (JE5331-00) | 5070 (JE5331-00) | 5070 (JE5331-00) | 5030 (JE5337-00) |
| 75 Adc | 5070 (JE5331-00) | 5070 (JE5331-00) | 5070 (JE5331-00) | 5030 (JE5337-00) |
| 100 Adc | 5070 (JE5331-00) | 5070 (JE5331-00) | 5030 (JE5337-00) | 5030 (JE5337-00) |
| 125 Adc | 5030 (JE5337-00) | 5030 (JE5337-00) | 5030 (JE5337-00) | n/a |
| 150 Adc | 5030 (JE5337-00) | 5030 (JE5337-00) | 5030 (JE5337-00) | 163 (JE5361-00) |
| 200 Adc | 5030 (JE5337-00) | 5030 (JE5337-00) | 5030 (JE5337-00) | 163 (JE5361-00) |
| 250 Adc | 5030 (JE5337-00) | 5030 (JE5337-00) | 163 (JE5361-00) | n/a |
| 300 Adc | 5030 (JE5337-00) | 5030 (JE5337-00) | 163 (JE5361-00) | 198 (JE5351-00) |
| 400 Adc | 163 (JE5361-00) | 163 (JE5361-00) | 163 (JE5361-00) | 198 (JE5351-00) |
| 500 Adc | 163 (JE5361-00) | 163 (JE5361-00) | 198 (JE5351-00) | n/a |
| 600 Adc | 163 (JE5361-00) | 198 (JE5351-00) | 198 (JE5351-00) | n/a |
| 800 Adc | 198 (JE5351-00) | 198 (JE5351-00) | 198 (JE5351-00) | n/a |
| 1000 Adc | 198 (JE5351-00) | 198 (JE5351-00) | 198 (JE5351-00) | n/a |
1.6.1 ATevo Weight Data
See online Product Literature JF5054-00 Product Literature) for ATevo weight data based on model (Vdc-Adc).
Three phase ATevo enclosures do not feature top-lifting eyes for moving. Using a forklift, relocate ATevo using the supplied shipping pallet. Lift ATevo enclosures from the bottom, between the mounting legs, into a final floor-mount installation.
Last modified:
18 September 2023