Disables the EQUALIZE output voltage mode which attempts to equalize the voltage among battery cells. This action can be triggered by either a binary or analog input. An example use-case for this feature would be when an aux input connected to a hydrogen sensor fires a 1% Hydrogen Alarm, this input can disable the EQUALIZE charging. This is presented as a new selection under the AUX INPUTS menu as an “Action” for either a binary input or an analog input, as seen in the figure below.

For more information about how to upgrade firmware, see either Section 6.5.4 or 6.5.5, depending on the ATevo product you purchased:

Last modified: 3 August 2023