Unless otherwise specified, the ATevo Auxiliary I/O Board (A4) will ship from the factory with the following Alarm Relay Configuration:
| Factory Default Alarm Relay Configuration | ||||
|---|---|---|---|---|
| Relay | Name | Latching | Delay | |
| . #1 | High DC Voltage | disabled | 30 seconds | |
| . #2 | Low DC Voltage | disabled | 30 seconds | |
| . #3 | DC Output Failure | disabled | 30 seconds | |
| . #4 | Low AC Supply (<65% nominal) | disabled | 30 seconds | |
| . #5 | Positive (+) Ground Fault | disabled | 30 seconds | |
| . #6 | Negative (-) Ground Fault | disabled | 30 seconds | |