The four (4) Binary Inputs are optically isolated from ATevo and each other. They can be configured via jumper selection to accept input voltages of 12Vdc, 24Vdc, 48Vdc, or 130Vdc (factory-default). Each Binary Input has an associated yellow LED and a jumper selection block. The LED serves as a debugging aid as it will illuminate when the associated Binary Input is high (in the ‘ON’ state).

The Binary Inputs may be configured to be active high or active low and generate alarms and controls such as charger shutdown. The configuration also permits each input to be assigned a custom name (such as ‘2% Hydrogen’, or ‘Vent Fan Fail’). ATevo will report all activity of the input (status, alarms or log files) by the generic default name or the custom configured name.

Last modified: 20 February 2024