- See also Service Instruction (JD5078-02).
The optional eliminator filter (C2) consists of a single electrolytic capacitor with two (2) wires connected directly to the Power Board (A2).
Preparation:
- Shut down and lock out all power to ATevo.
- Remove safety shield and check with a voltmeter.
- Locate the ‘blue can’ capacitor (C2), at the bottom-left of ATevo, secured to the galvanized base with two (2) nylon zip ties.
Removal of Existing Capacitor:
- Cut the plastic ties and disconnect wires from the Power Board (A2).
- Remove the wired capacitor. Replacement capacitor (C2) is supplied with new wires and pre-crimped terminals.
Installation of Replacement Capacitor Assembly:
- Connect wires of new capacitor assembly (C2) to Power Board.
- Mount replacement cap to ATevo base with provided wire ties.
- Replace safety shield, and close front panel door.
- Restart ATevo.
Last modified:
2 August 2023
Need more help with this?
Don’t hesitate to contact us here.