Network Operation with Remote PLC

PLC Assembly Inputs


Input Assembly ID 103

Register Name Internal Address Assembled PLC Address Description
Motor Status 4:0161 M: 4:1300

E: I.Data [0]

P: Byte 0,1
Bitwise Value
Bit 00 Reserved
Bit 01 Motor Stopped
Bit 02 – Bit 06 Reserved
Bit 07 – Bit 09 Speed Units – See topic Speed Units for details
Bit 10 – 15 Reserved
Error Status 4:0162 M: 4:1301

E: I.Data [1]

P: Byte 2,3
Bitwise Value
Bit 00 Motor Not Ready
Bit 01 Input Power Voltage Out of Range
Bit 02 Motor Overheat
Bit 03 – 15 Reserved
Measured Current 4:0166 M: 4:1302

E: I.Data [2]

P: Byte 4,5
Measured motor current in 0.1A increments (eg. 34 = 3.4A)
Measured RPM 4:0167 M: 4:1303

E: I.Data [3]

P: Byte 6,7
Measured motor tube RPM
Reserved 4:0168 M: 4:1304

E: I.Data [4]

P: Byte 8,9
Reserved 4:0169 M: 4:1305

E: I.Data [5]

P: Byte 10,11
Reserved 4:0170 M: 4:1306

E: I.Data [6]

P: Byte 12,13
Reserved 4:0171 M: 4:1307

E: I.Data [7]

P: Byte 14,15
Reserved 4:0172 M: 4:1308

E: I.Data [8]

P: Byte 16,17
Current Output Power 4:0173 M: 4:1309

E: I.Data [9]

P: Byte 18,19
Current Output Power in 0.1W increments (eg. 574 = 57.4W)
Digital Inputs 4:0174 M: 4:1310

E: I.Data [10]

P: Byte 20,21
Bitwise Value
Bit 00 Enable
Bit 01 Run
Bit 02 Clear Error
Bit 03 User Profile 0
Bit 04 User Profile 1
Bit 05 Main Port Pin 4
Bit 06 Main Port Pin 2
Bit 07 Aux Port Pin 4
Bit 08 Aux Port Pin 2
Bit 09 – 15 Reserved
I/O Faults 4:0175 M: 4:1311

E: I.Data [11]

P: Byte 22,23
Bitwise Value
Bit 00 Main or Aux Port Overload
Bit 01 Main Port Short Circuit
Bit 02 Aux Port Short Circuit
Bit 03 Motor Error Output Short Circuit
Bit 04 Motor Running Output Short Circuit
Bit 05 – 15 Reserved
Logic Power Voltage 4:0176 M: 4:1312

E: I.Data [12]

P: Byte 24,25
Logic Power Voltage in 0.1V increments (eg. 486 = 48.6V)
Motor Power Voltage 4:0177 M: 4:1313

E: I.Data [13]

P: Byte 26,27
Motor Power Voltage in 0.1V increments (eg. 249 = 24.9V)
Motor Voltage 4:0178 M: 4:1314

E: I.Data [14]

P: Byte 28,29
Motor Voltage Voltage in 0.1V increments (eg. 362 = 36.2V)
Motor Temperature 4:0179 M: 4:1315

E: I.Data [15]

P: Byte 30,31
Motor Temperature in 0.1ºC increments (e.g. 585 = 58.5ºC)
Compensator Temperature 4:0180 M: 4:1316

E: I.Data [16]

P: Byte 32,33
Compensator Temperature in 0.1ºC increments (e.g. 263 = 26.3ºC)
MCU temperature 4:0181 M: 4:1317

E: I.Data [17]

P: Byte 34,35
MCU Temperature in 0.1ºC increments (e.g. 345 = 34.5ºC)
Power Stage Temperature 4:0182 M: 4:1318

E: I.Data [18]

P: Byte 36,37
Power Bus Stage Temperature in 0.1ºC increments (e.g. 432 = 43.2ºC)
Reserved 4:0183 M: 4:1319

E: I.Data [19]

P: Byte 38,39
Reserved 4:0184 M: 4:1320

E: I.Data [20]

P: Byte 40,41
Upstream Module Status 4:0134 M: 4:1321

E: I.Data [21]

P: Byte 42,43
See topic Upstream / Downstream Status & Tracking for details
Downstream Module Status 4:0232 M: 4:1322

E: I.Data [22]

P: Byte 44,45
Current Tracking Word 1

Adjacent Upstream Module
4:0139 M: 4:1323

E: I.Data [23]

P: Byte 46,47
Current Tracking Word 2

Adjacent Upstream Module
4:0140 M: 4:1324

E: I.Data [24]

P: Byte 48,49
Current Module Reset Count N/A M: 4:1325

E: I.Data [25]

P: Byte 50,51
See topic Current Module Reset Count for details