- All battery chargers must be ATevo Series. The ATevo forced load sharing feature will not operate with legacy AT10.1 and AT30 Series battery chargers.
- All connected chargers must have the same voltage settings, have the same dc output current rating, and have the same version of ATevo Main Control Board (A1) firmware.
- Each ATevo requires a ‘FLS’ Serial Communications Adapter (A13) to be installed in either Port 2 or Port 3 of the Main Control Board (A1).
Last modified:
2 August 2023