Register Name / Module Address Assembled Address for PLC Description
Set Status to Downstream Module
4:0196
M: 4:1817
E: O.Data [17]
P: Byte 34 (Hi)
   Byte 35 (Lo)
Used to write ConveyLinx Module ZPA Status to Downstream ERSC:
4 = Instruct Downstream ConveyLinx Module to “wake-up” and run its most upstream zone
1 = Instructs Downstream ConveyLinx Module that carton has exited local zone and to accept any tracking data written in Set Discharge Tracking Word 1 / Word 2 registers when carton arrives
Set Status to Upstream Module
4:0116
M: 4:1818
E: O.Data [18]
P: Byte 36 (Hi)
   Byte 37 (Lo)
Used to write ConveyLinx Module’s ZPA Status to Upstream ConveyLinx Module:
5 = Instructs Upstream ConveyLinx Module’s discharge zone to accumulate and hold any carton that arrives at its discharge zone.
1 = Instructs Upstream ConveyLinx Module’s discharge zone to release any carton that arrives at its discharge zone
Set Discharge Tracking Word 1
4:0201
M: 4:1820
E: O.Data [20]
P: Byte 40 (Hi)
   Byte 41 (Lo)
Only used when local PLC I/O Mode ConveyLinx Module needs to pass tracking data to a downstream connected ConveyLinx Module. Used in conjunction with Set Status to Downstream Module register
Set Discharge Tracking Word 2
4:0202
M: 4:1821
E: O.Data [21]
P: Byte 42 (Hi)
   Byte 43 (Lo)
Reserved M: 4:1822
E: O.Data [22]
P: Byte 44 (Hi)
   Byte 45 (Lo)