The Filtering Board assembly (A7) consists of a capacitor bank (C1x) and bleed resistor (R9x) mounted on a printed circuit board.
Preparation:
- Shut down and lock out all power to ATevo.
- Remove safety shield.
- Locate capacitor board assembly on top of heatsink, above power board and rectifier along left side of ATevo.
Removal of Existing Capacitor Board Assembly:
- Remove (2) nuts from studs connecting Power Board (A2) to Capacitor Board (A7).
- Remove (1) screw at top center of Capacitor Board.
- Remove existing capacitor board assembly.
Installation of New Capacitor Board Assembly:
- Place new Capacitor Board Assembly (A7) onto studs on Power Board (A2) and replace (2) nuts and (1) screw.
- Replace safety shield, close front panel door, and restart ATevo.
Last modified:
4 March 2021