The optional eliminator filter (C2) consists of a single ‘blue can’ electrolytic capacitor with two (2) wires that connect to Power Board.
Preparation:
- Shut down and lock out all power to ATevo.
- Remove safety shield.
- Locate capacitor (C2) at bottom-left of enclosure, mounted with two (2) wires to ATevo base.
Removal of Existing Capacitor:
- Cut the plastic ties and disconnect wires from the Power Board (A2). Remove the wired capacitor. Replacement capacitor (C2) is supplied with new wires and pre-crimped terminals.
Installation of Replacement Capacitor Assembly:
- Connect wires of new capacitor assembly (C2) to Power Board.
- Mount replacement cap to ATevo base with provided wire ties.
- Replace safety shield, close front panel door, and restart ATevo.
Last modified:
4 March 2021
Need more help with this?
Don’t hesitate to contact us here.