• Shut down and lock out all power to ATevo.
  • Remove safety shield.
  • DC Power Supply Board (P/S-9V) is plugged onto bottom center of Power Board (A2), directly below L2-2 lug.
  • Gently pull Power Supply Board off of Power Board (A2).
  • Align two (2) header sockets (on bottom of replacement DC Power Supply) with J101 and J102 header pin strips on existing Power Board.
  • Gently press new DC Power Supply Board (P/S-9V) onto Power Board (A2) until it mates.
  • Replace safety shield and close front panel door.
  • Restart ATevo.
Last modified: 4 March 2021