- Shut down and lock out all power to ATevo.
- Remove safety shield.
- DC Power Supply Board (P/S-9V) is plugged onto bottom center of Power Board (A2), directly below L2-2 lug.
- Gently pull Power Supply Board off of Power Board (A2).
- Align two (2) header sockets (on bottom of replacement DC Power Supply) with J101 and J102 header pin strips on existing Power Board.
- Gently press new DC Power Supply Board (P/S-9V) onto Power Board (A2) until it mates.
- Replace safety shield and close front panel door.
- Restart ATevo.