Register Name / Module Address | Assembled Address for PLC | Description |
---|---|---|
ConveyStop Command Word 4:0020 |
M: 4:1619 E: O.Data [19] P: Byte 38 (Hi) Byte 39 (Lo) |
Integer Value: 0 = No Command 1 = Command local module’s Stop Group to go to Stopped State 2 = Command Local Module’s Stop Group to Clear Stopped State |
Clear Sensor Jam for Local Upstream Zone 4:0109 |
M: 4:1620 E: O.Data [20] P: Byte 40 (Hi) Byte 41 (Lo) |
Use when PLC detects a local Upstream jam in Module Status Word #1 Bit 5: PLC creates transition from 0 to 1 to send command to local upstream zone to clear the jam condition |
Clear Sensor Jam for Local Downstream Zone 4:0189 |
M: 4:1621 E: O.Data [21] P: Byte 42 (Hi) Byte 43 (Lo) |
Use when PLC detects a local Downstream jam in Module Status Word #2 Bit 5: PLC creates transition from 0 to 1 to send command to local downstream zone to clear the jam condition |