Register Name / Module Address Assembled Address for PLC Description
ConveyStop Command Word
4:0020
M: 4:1619
E: O.Data [19]
P: Byte 38 (Hi)
   Byte 39 (Lo)
Integer Value:
   0 = No Command
   1 = Command local module’s Stop Group to
       go to Stopped State
   2 = Command Local Module’s Stop Group to
       Clear Stopped State
Clear Sensor Jam for Local Upstream Zone
4:0109
M: 4:1620
E: O.Data [20]
P: Byte 40 (Hi)
   Byte 41 (Lo)
Use when PLC detects a local Upstream jam in Module Status Word #1 Bit 5:
   PLC creates transition from 0 to 1 to send command to local upstream zone to clear the jam condition
Clear Sensor Jam for Local Downstream Zone
4:0189
M: 4:1621
E: O.Data [21]
P: Byte 42 (Hi)
   Byte 43 (Lo)
Use when PLC detects a local Downstream jam in Module Status Word #2 Bit 5:
   PLC creates transition from 0 to 1 to send command to local downstream zone to clear the jam condition