The following table lists Binary Outputs (Object 10):

Binary Output Status Points
Object Number Status 10
Binary Output Status Points 1(read)
Default Variation reported when variation 0 requested 2 (Binary Output Status)
Control Relay Output Blocks
Object Number 12
Request Function Codes supported: 3 (select), 4 (operate)
5 (direct operate),
6 (direct operate, noack)
Point Index Name/Description Latch ‘OFF Latch ‘ON’
0 Float / Equalize Mode float equalize
1 (not used) - -
2 (not used) - -
3 Manual Timer / Auto Equalize Timer manual auto
4 HVDC Shutdown disable enable
5 (not used) - -
6 Battery Temperature Compensation (TempCo) Enable disable enable
7 Battery Discharge Enable disable enable
8 Remote Voltage Sense Enable disable enable
9 Auto Run Battery Open Test Enable disable enable
10 Battery Open Test Ran disable enable
11 Dynamic Current Limit Enable disable enable
12 Battery Temperature Probe Enable disable enable
- future