The following table lists Binary Outputs (Object 10):
| Binary Output Status Points | |||
|---|---|---|---|
| Object Number Status | 10 | ||
| Binary Output Status Points | 1(read) | ||
| Default Variation reported when variation 0 requested | 2 (Binary Output Status) | ||
| Control Relay Output Blocks | |||
| Object Number | 12 | ||
| Request Function Codes supported: | 3 (select), 4 (operate) | ||
| 5 (direct operate), 6 (direct operate, noack) |
|||
| Point Index | Name/Description | Latch ‘OFF’ | Latch ‘ON’ |
| 0 | Float / Equalize Mode | float | equalize |
| 1 | (not used) | - | - |
| 2 | (not used) | - | - |
| 3 | Manual Timer / Auto Equalize Timer | manual | auto |
| 4 | HVDC Shutdown | disable | enable |
| 5 | (not used) | - | - |
| 6 | Battery Temperature Compensation (TempCo) Enable | disable | enable |
| 7 | Battery Discharge Enable | disable | enable |
| 8 | Remote Voltage Sense Enable | disable | enable |
| 9 | Auto Run Battery Open Test Enable | disable | enable |
| 10 | Battery Open Test Ran | disable | enable |
| 11 | Dynamic Current Limit Enable | disable | enable |
| 12 | Battery Temperature Probe Enable | disable | enable |
| - | future | – | – |