The following table lists Binary Outputs (Object 10):
Binary Output Status Points | |||
---|---|---|---|
Object Number Status | 10 | ||
Binary Output Status Points | 1(read) | ||
Default Variation reported when variation 0 requested | 2 (Binary Output Status) | ||
Control Relay Output Blocks | |||
Object Number | 12 | ||
Request Function Codes supported: | 3 (select), 4 (operate) | ||
5 (direct operate), 6 (direct operate, noack) |
|||
Point Index | Name/Description | Latch ‘OFF’ | Latch ‘ON’ |
0 | Float / Equalize Mode | float | equalize |
1 | (not used) | - | - |
2 | (not used) | - | - |
3 | Manual Timer / Auto Equalize Timer | manual | auto |
4 | HVDC Shutdown | disable | enable |
5 | (not used) | - | - |
6 | Battery Temperature Compensation (TempCo) Enable | disable | enable |
7 | Battery Discharge Enable | disable | enable |
8 | Remote Voltage Sense Enable | disable | enable |
9 | Auto Run Battery Open Test Enable | disable | enable |
10 | Battery Open Test Ran | disable | enable |
11 | Dynamic Current Limit Enable | disable | enable |
12 | Battery Temperature Probe Enable | disable | enable |
- | future | – | – |