2.1 DNP3 Overview
Communications options support DNP3 Level 2 protocol and change events with unsolicited messaging.
Serial Settings Supported | ||
---|---|---|
Parity | Data Bits | Stop Bits |
no | 8 | 1 |
no | 8 | 2 |
even | 8 | 1 |
odd | 8 | 1 |
Refer to Section 5 regarding DNP3 protocol and point list.
2.2 Modbus Overview
Communications options can be set to communicate on standard Modbus networks using either of two transmission modes:
Transmission Mode | Advantage of Mode | Serial Settings Supported | ||
---|---|---|---|---|
ASCII | less strict serial timing requirements without causing errors | Parity | Data Bits | Stop Bits |
no | 7 | 2 | ||
even | 7 | 1 | ||
odd | 7 | 1 | ||
RTU | higher throughput than ASCII due to more data transmission with less overhead | Parity | Data Bits | Stop Bits |
no | 8 | 1 | ||
no | 8 | 2 | ||
even | 8 | 1 | ||
odd | 8 | 1 |
Refer to Section 6 regarding Modbus protocol and register set.
Last modified: