Wall-mounting is only an option for the Style-5070 enclosure. When wall-mounting this style ATevo, consider the following:
- Refer to Outline Drawing Style-5070 Enclosure and Installation Instructions for Style-2/5018 Wall-Mounting Bracket Accessory
- Wall must be strong enough to properly support ATevo’s weight, plus a safety factor. Refer to Weight Table in Section 3.4, Moving ATevo. The weight of your ATevo may be different, depending on the features, options, and accessories ordered with the unit.
- Select conduit entrances with planned AC input and DC output wiring in mind. By using pre-fab knockouts on enclosure sides or bottom, the enclosure shroud can be removed for internal servicing without removing ATevo from the wall.
- Location requirements:
- Free of drips and splatter. If falling particles and liquids are a problem, install a NEMA Type-2 drip shield accessory.
- Between 0 and 122 °F / -18 and 50 °C, with relative humidity between 0% and 95% non-condensing.
- Must be free of flammable or explosive materials.
- Maintain at least 6in / 152mm of free air on all vented surfaces for cooling.
- Allow at least 36in / 914mm front clearance for operation and maintenance.
PROCEDURE
- Install two (2), 11-gauge steel wall-mounting brackets to the wall according to the diagram in Installation Instructions for Style-2/5018 Wall-Mounting Bracket Accessory.
- Use four (4) supplied 0.5in x 2.00in (12.7mm x 50.8mm) WWTB screws and additional hardware to mount the bottom of the ATevo Style-5070 enclosure to the wall-mounting brackets as shown in Installation Instructions for Style-2/5018 Wall-Mounting Bracket Accessory.
Last modified:
8 March 2021