- Shut down and lock out all power to the ATevo.
- Remove the safety shield.
- The MOV Board (A9) is bolted to top left side of circuit breaker bracket.
- Remove the two (2) screws that connect the Transformer (T1) primary wire lugs to the MOV Board (A9).
- Remove the bolt that mounts the MOV Board (A9) to the breaker bracket.
- Bolt the new MOV Board (A9) onto the breaker bracket.
- Install the two (2) screws through the lugs that connect MOV Board to the primary wires and tighten nuts.
- Replace the safety shield and close the front panel door.
- Restart the ATevo.
Last modified:
4 March 2021