The combination of signals on the Run A and Run B terminals allows you to dynamically set the speed with your digital run signals to the EQUBE Module module. The following chart lists the signal states and their respective speed control:

Run A Run B Description
ON OFF Start motor and run at 100% of the speed selected on DIP Switches 1 thru 5
ON ON Start motor and run at 75% of the speed selected on DIP Switches 1 thru 5
OFF ON Start motor and run at 50% of the speed selected on DIP Switches 1 thru 5
OFF OFF Stop motor