Register Name / Module Address | Assembled Address for PLC | Description |
---|---|---|
Sensor & Control Port Inputs 4:0035 |
M: 4:1518 E: I.Data [18] P: Byte 36 (Hi) Byte 37 (Lo) |
Bitwise Value – Read Only: bit 0 = Left AUX Input (Terminal 4) bit 2 = Right AUX Input (Terminal 4) bit 4 = Left SEN Input (Terminal 2) bit 6 = Right SEN Input (Terminal 2) bit 15 = 2 sec on / 2 sec off heatbeat All other bits reserved |
Sensor Detect 4:0036 |
M: 4:1523 E: I.Data [23] P: Byte 46 (Hi) Byte 47 (Lo) |
Bitwise Value – Read Only: bit 0 = Right Port Sensor Detected bit 1 = Left Port Sensor Detected All other bits reserved |
Reserved | M: 4:1519 E: I.Data [19] P: Byte 38 (Hi) Byte 39 (Lo) |
|
ConveyStop Status 4:0019 |
M: 4:1520 E: I.Data [20] P: Byte 40 (Hi) Byte 41 (Lo) |
Bitwise Value – Read Only: bit 0 – 4 Reserved bit 5 = Stop active on another module in Stop Group bit 6 = Stop active due to lost communication connection bit 7 = Stop active due to lost PLC connection bit 8 = Stop active on local module’s Left Control Port bit 9 = Stop active on local module’s Right Control Port bit 10 = Stop active due to Stop Command from PLC bit 11 – 15 Reserved |
ConveyMerge Left Status 4:0459 |
M: 4:1521 E: I.Data [21] P: Byte 42 (Hi) Byte 43 (Lo) |
Integer Value – Read Only: 1 = Left Merge Not Releasing 6 = Left Merge Releasing |
ConveyMerge Right Status 4:0475 |
M: 4:1522 E: I.Data [22] P: Byte 44 (Hi) Byte 45 (Lo) |
Integer Value – Read Only: 1 = Right Merge Not Releasing 6 = Right Merge Releasing |