DNP3 Overview

Communications options support DNP3 Level 2 protocol and change events with unsolicited messaging. Refer to Section 4 regarding DNP3 protocol and point list.

Serial Setting Supported
Parity Data Bits Stop Bits
no 8 1
no 8 2
even 8 1
odd 8 1

Modbus Overview

Communications options can be set to communicate on standard Modbus networks using either of two transmission modes:

Transmission Mode Advantage of Mode Serial Setting Supported
ASCII less strict serial timing requirements without causing errors Parity Data Bits Stop Bits
no 7 2
even 7 1
odd 7 1
RTU higher throughput than ASCII due to more data transmission with less overhead Parity Data Bits Stop Bits
no 8 1
no 8 2
even 8 1
odd 8 1

Refer to Section 5 regarding Modbus protocol and register set.