07/24/2024 – Main v3.2.0, UI 3.2.0
- Extra information included in alarm log. “Discharge end” event now includes:
◦ Ah removed
◦ Discharge timespan
◦ Battery voltage at end of discharge - “Auto equalize after” set point added to Advanced Settings menu. The value has a rangeof 0.1 to 10.0 hours. The setting specifies the amount of time that AC input is absent before activating auto equalize if that feature is enabled. Auto equalize previously activated after 12s of AC loss. It now defaults to 6 minutes (0.1 hours) if auto equalize is enabled.
- “Display temp as F” setting added to System Settings menu.
- Web Server support added along with Web Access menu.
Last modified:
6 May 2025