The Analog Input Action assignment links the analog input alarm to a charger control. Examples of a charger control include charger shutdown or float/equalize mode control. ATevo will execute the charger control when the analog input alarm is in the active state.
To assign a control to an analog input:
MENU > AUX INPUTS > ‘Analog Input Configuration’ > select input (refer to Section 12.6.1) > ‘Action:’ > select action

Disable Equalize
Disables the EQUALIZE output voltage mode which attempts to equalize the voltage among battery cells. This action can be triggered by either a binary or analog input. An example use-case for this feature would be when an aux input connected to a hydrogen sensor fires a 1% Hydrogen Alarm, this input can disable the EQUALIZE charging. 

For more information about how to upgrade firmware, see either Section 6.5.4 or 6.5.5, depending on the ATevo product you purchased:
- Originally supplied with firmware v2.6.6 or earlier
- Originally supplied with firmware v2.7.0 or later