The Analog Input Action assignment links the analog input alarm to a charger control. Examples of a charger control include charger shutdown or float/equalize mode control. ATevo will execute the charger control when the analog input alarm is in the active state.

To assign a control to an analog input:
MENU > AUX INPUTS > ‘Analog Input Configuration’ > select input (refer to Section 12.6.1) > ‘Action:’ > select action

Disable Equalize

Disables the EQUALIZE output voltage mode which attempts to equalize the voltage among battery cells. This action can be triggered by either a binary or analog input. An example use-case for this feature would be when an aux input connected to a hydrogen sensor fires a 1% Hydrogen Alarm, this input can disable the EQUALIZE charging. This is presented as a selection under the AUX INPUTS menu as an “Action” for either a binary input or an analog input, as seen in the figure below.

For more information about how to upgrade firmware, see either Section 6.5.4 or 6.5.5, depending on the ATevo product you purchased: