Module Configuration Tabs / Sensors / ConveyLinx-ECO Family /


ConveyLinx ERSC ConveyLinx-Ai 24V ConveyLinx-Ai 48V
ConveyLinx-ECO ZPA Mode PLC I/O Mode


Learn more details about Lane Full Interface functionality



Assuming the most downstream zone is connected to the Left side of the module; we set the Left Aux I/O Pin 2 to Lane Full Interface from the drop-down box and make sure we click the “DOWN” arrow to indicate that the Left Pin 2 signal is to be associated with the Downstream Zone. The signal must be energized for the Block time period before cartons will stop and accumulate and the signal must be de-energized for the Clear time period before cartons will be allowed to release. In this example, we entered 5 seconds for the Block Time and 6 seconds for the Clear Time